Oil-Immersed Transformers · ANSI/LatAm Standard

1000 kVA 13.8kV 60Hz ANSI Three-Phase Oil-Immersed Transformer

This 1000 kVA 60 Hz oil-immersed transformer is configured for ANSI and Latin American grid standards. Suitable for utility distribution, industrial, and infrastructure projects operating at 60 Hz. Designed to ANSI/IEEE C57.12 guidelines with IEC 60076 cross-reference. Export-ready from Hefei, China.

기술 사양

정격 용량 1000 kVA
Primary Voltage (U1) 11,000 V (11 kV)
Secondary Voltage (U2) 415 V / 240 V (3-Phase 4-Wire)
Vector Group Dyn11
정격 주파수 50 Hz
냉각 방식 ONAN (Oil Natural Air Natural)
Primary Current (I1) 17.49 A
Secondary Current (I2) 1391.2 A
Guaranteed No-Load Loss (P0) 1150 W
Guaranteed Load Loss (Pk at 75°C) 8100 W
Short-Circuit Impedance (Uk) 4.5%
HV Insulation Level LI 75 / AC 35 (11kV Class)
Temperature Rise Limits Top Oil ≤ 50K, Winding ≤ 55K (45°C Ambient)
Creepage Distance ≥ 31 mm/kV (Outdoor Tropicalized Porcelain)
Core & Coil Weight 1650 kg
Insulating Oil Weight 920 kg
Total Assembled Weight 3200 kg
Overall Footprint (L×W×H) 1650 mm × 1050 mm × 1750 mm
Governing Standards IEC 60076, BS 171, SON NIS, NERC Code

제품 정보

상태

게시됨

제품 ID

1000_KVA_13_8KV_60HZ_ANSI_THREE_PHASE_OIL_IMMERSED_TRANSFORMER

최종 업데이트

2026-05-17T04:26:02.882452

Application Scenarios

  • Latin American utility distribution and rural electrification projects
  • Industrial facilities operating on 60 Hz ANSI power systems
  • EPC contractor packages for Americas and Caribbean infrastructure
  • Renewable energy grid connection in 60 Hz markets

Key Features

  • 1000 kVA rated capacity configured for 60 Hz ANSI and Latin American grids
  • high voltage class matching standard ANSI distribution voltages
  • Designed to ANSI/IEEE C57.12 guidelines with IEC 60076 cross-reference capability
  • 60 Hz frequency rating for Americas, Caribbean, and parts of Southeast Asia
  • Copper or aluminum winding available; pad-mount and substation configurations supported

자주 묻는 질문

Please send us your required capacity, high voltage, low voltage (V), frequency (Hz), cooling method, vector group, tapping range, installation conditions, and destination country. We will respond with a configuration and indicative pricing within 24 hours.

The product can be produced according to IEC standards and customer technical specifications. Routine factory tests, insulation resistance, ratio, and load loss verification are standard. Type test reports available on request.

The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Sea freight, air freight, and land transport options are available. Lead time is project-dependent and confirmed at order stage.

기준 및 규정 준수

The product can be produced according to IEC standards and customer technical specifications. Routine factory tests, insulation resistance, ratio, and load loss verification are standard. Type test reports available on request.

포장, 배송 및 서비스

The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Sea freight, air freight, and land transport options are available. Lead time is project-dependent and confirmed at order stage.

Please send us your required capacity, high voltage, low voltage (V), frequency (Hz), cooling method, vector group, tapping range, installation conditions, and destination country. We will respond with a configuration and indicative pricing within 24 hours.

진행할 준비가 되셨나요?

견적 요청 1000 kVA 13.8kV 60Hz ANSI...

프로젝트 범위를 공유해 주시면 24시간 이내에 답변드리겠습니다.