Oil-Immersed Transformers · Distribution

50 kVA 33kV Three-Phase Oil-Immersed Distribution Transformer

This 50 kVA oil-immersed distribution transformer is designed for reliable power distribution in rural utility networks, industrial feeders, and infrastructure projects across Africa, MENA, and other grid markets. ONAN cooling with IEC 60076 design reference. Export-ready from Hefei, China.

المواصفات الفنية

السعة المقدرة 50 kVA
Primary Voltage (U1) 33,000 V (33 kV)
Secondary Voltage (U2) 415 V / 240 V (3-Phase 4-Wire)
Vector Group Dyn11
التردد المقنن 50 Hz
طريقة التبريد ONAN (Oil Natural Air Natural)
Primary Current (I1) 0.87 A
Secondary Current (I2) 69.6 A
Guaranteed No-Load Loss (P0) 130 W
Guaranteed Load Loss (Pk at 75°C) 850 W
Short-Circuit Impedance (Uk) 4.0%
HV Insulation Level LI 170 / AC 70 (33kV Class)
Temperature Rise Limits Top Oil ≤ 50K, Winding ≤ 55K (45°C Ambient)
Creepage Distance ≥ 31 mm/kV (Outdoor Tropicalized Porcelain)
Core & Coil Weight 230 kg
Insulating Oil Weight 160 kg
Total Assembled Weight 450 kg
Overall Footprint (L×W×H) 950 mm × 650 mm × 1200 mm
Governing Standards IEC 60076, BS 171, SON NIS, NERC Code

معلومات المنتج

الحالة

نُشر

معرف المنتج

50_KVA_33KV_THREE_PHASE_OIL_IMMERSED_DISTRIBUTION_TRANSFORMER

آخر تحديث

2026-05-17T04:26:02.882452

Application Scenarios

  • Rural utility distribution network feeders
  • Industrial and mining site power supply
  • Infrastructure and EPC contractor projects in Africa and MENA
  • Renewable energy grid connection at voltage class

Key Features

  • 50 kVA rated capacity for rural utility and distribution network applications
  • class design suited for Africa, MENA, and IEC-standard grid markets
  • Oil-immersed ONAN structure for stable thermal performance in outdoor environments
  • Copper or aluminum winding options available to suit project budget requirements
  • Off-circuit tap changer with +/-2 x 2.5% or +/-5% range as standard

الأسئلة الشائعة

Please send us your required capacity, high voltage, low voltage (V), frequency (Hz), cooling method, vector group, tapping range, installation conditions, and destination country. We will respond with a configuration and indicative pricing within 24 hours.

The product can be produced according to IEC standards and customer technical specifications. Routine factory tests, insulation resistance, ratio, and load loss verification are standard. Type test reports available on request.

The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Sea freight, air freight, and land transport options are available. Lead time is project-dependent and confirmed at order stage.

المعايير والامتثال

The product can be produced according to IEC standards and customer technical specifications. Routine factory tests, insulation resistance, ratio, and load loss verification are standard. Type test reports available on request.

التغليف والتسليم والخدمة

The product is prepared for export shipment with suitable packing and transport arrangements based on destination and handling requirements. Sea freight, air freight, and land transport options are available. Lead time is project-dependent and confirmed at order stage.

Please send us your required capacity, high voltage, low voltage (V), frequency (Hz), cooling method, vector group, tapping range, installation conditions, and destination country. We will respond with a configuration and indicative pricing within 24 hours.

هل أنت مستعد للمتابعة؟